The microSpider2 Industrial is a complete data logging and telemetry system. It includes all software, hardware, backup battery and a built-in mobile phone module. The enclosure fits standard DIN rail brackets.
The microSpider2 Industrial can
- monitor inputs (analogue, digital, counters, frequency, quadrature/shaft encoder)
- control outputs
- generate SMS, email and twitter alarms
- record data
- send data via e-mail, FTP and HTTP
- communicate via internal 3G/4G modem
- charge an external SLA battery via a built-in solar panel / mains charger
- update software automatically in-field from remote servers, or update from connected pc.
The microSpider2 Industrial is ideal for long term monitoring and can interface with a wide range of sensors and meters. the browser interface makes it easy to set up and test. It can be powered from 12v dc.
The microSpider2 Industrial logs data and automatically sends reports via email or ftp. Any alarms can activate outputs, send SMS and email alarm messages as well as historical reports
Economical – low upfront, installation and operational costs
Easy to use – simple familiar web browser interface
Easy to install
Integrated mounting – DIN rail compatible.
Simply connect antenna, battery / supply and inputs.
No special software required
setup and download using browser
can be managed remotely (requires LiveSMS option)
reports sent straight to your PC or server
text/csv reports open in Excel
receive reports via email, FTP and HTTP
No licenses, royalties or service agreements
Large internal memory – full local backup of data
Physical
Dimensions: (approx) 156(L) x 60(H) x 87 (W) mm
Weight: (approx) 500 g
Operating temperature: -5 to +50 degrees Celsius
Data Recorder
Capacity: approximately 400,000 records
Storage memory: Non-volatile FLASH
Time resolution: 1 second
Download format: CSV file
Power Supply
Operating voltage:
Nominal 12V DC, min 1A
Power consumption:
Standby 65 uA
Active <3mA (modem off, LAN powered externally)
Active 100mA (modem on, LAN powered internally)
Active 250mA (modem on, communicating)
Integrated battery charger regulator:
Charges an external 12V SLA battery from an external 12V solar panel or a 16 - 30V DC 2A
power source
Backup battery:
Internal, user replaceable 9V battery (optional)
Warranty
Factory backup 12 months parts and labour guarantee
Inputs
Number of inputs:
- Up to 4 digital
- Up to 4 analog
- 4 system inputs
- Up to 20 SDI-12 / Modbus (with optional SDI-12/Modbus Interface)
Digital Inputs:
- 0 - 12V DC Voltage or voltage-free switch contact
- Can be used as switch, event (rainfall), counter or utility meter inputs (user selectable)
Analogue Inputs: Resolution 12 bits
- 4 - 20 mA, common ground
- 0 - 2.4V, common ground
- 0 - 5V, common ground
- 0 - 10V, common ground
Counter / Event Inputs
- Minimum pulse width: 5 ms
- Maximum frequency: 100 Hz
- Range: 0 - 999,999
System Inputs:
- System temperature
- External battery voltage
- Charger voltage
- LAN power voltage
Outputs
Number of outputs 3
- 1 x Switched power for sensor power / control
- 1 x Open collector for accessory control
- 1 x Low power sensor supply (3.3V or 5V)
Alarms
Number of alarms: 16
Type: SMS, twitter and/or e-mail transmission
Trigger: User definable input and trigger point
SMS / e-mail / twitter text: 1 per alarm, user definable
Number of phone numbers: 3 per alarm, user definable
Number of e-mail addresses 2 per alarm, user definable
Communication Interfaces
Ethernet 10/100 base-T, RJ-45 connector
Cellular phone module: Built-in 4G, 3G or Iridium satellite
Antenna: internal antenna - External antenna, SMA connector
Internet connectivity: 4G, 3G, LAN
Product is available in a variety of configurations to suit your needs, you may specify any of the following:
- 4G/3G or Iridium satellite communications
- Live SMS
Provides remote access from a web browser or mobile phone and extends the SMS capabilities of the microSpider2. Features include alarm acknowlegement, control activation and the ability to schedule modem power ups to create communication windows. - DNP3
Compliant with Level 2 of the DNP3 standard, supporting all of the microSpider2's inputs and controls, the DNP3 option allows the microSpider2 to communicate with a SCADA system via 4G/3G modem or local area network.
Accessories
Weatherproof enclosure
SDI-12/Modbus Interface
GPS Interface
Solar panel
Range of external 4G/3G Antennae
Software
microSpider2 Industrial Software v1.95 (Zip File)
Manuals / Brochures
microSpider2 Industrial Brochure
microSpider2 Industrial Quick Start Guide
microSpider2 Manual V1.26
DNP3
microSpider2 XML Device Profile (Zip file)